Instruction, Operation,
and Maintenance
Manual
Fulton Gas Fired Steam
Boilers
HP to 60 HP
Serial Number: _______________________________
Model Number: _______________________________
Fulton Order Number: _______________________________
Sold To: _______________________________
Job Name: _______________________________
Date: _______________________________
Seitenansicht 0
1 2 3 4 5 6 ... 101 102

Inhaltsverzeichnis

Seite 1

Instruction, Operation, and MaintenanceManualFulton Gas Fired SteamBoilers  HP to 60 HPSerial Number: _______________________________Model Number:

Seite 2

4-G 1/01

Seite 4

Component Data Sheets7-G 1/01

Seite 6

5-G 1/01Safety Warnings/PrecautionsSafety Warnings Cautions &NotesThe following WARNINGS, CAUTIONS, and NOTES appear in various chapters of thi

Seite 8 - 2-G 1/01

7-G 1/01Description/InstructionsLE

Seite 9

8-G 1/01

Seite 10 - 4-G 1/01

Standard Models ICS/FB-A 9.5 10 15 20 25 30Models ICX/FB-F 9.5 10 15 20 30Unit Size: BHP 9.5 10 15 20 25 30A. Boiler Height IN 67.5 63.5 69 72.5 74.5

Seite 11 - Safety Warnings/Precautions

SpecificationsModels ICS/ICX/FB 9.5 10 15 20 25 30Boiler ConnectionsN. Steam Outlet 15 PSI N/A 1.5” 2” 3” 3” 3”NPT NPT CL150# CL150# CL150#Flange Fla

Seite 12 - 6-G 1/01

11-G 1/01OperationLE

Seite 14 - 8-G 1/01

13-G 1/01Starting the Gas Fired BoilerSee page 44-GGas Burner Set Upa. Open the manual gas cocks onthe pilot and main lines of the gashead.b. Switch

Seite 17 - Operation

15-G 1/01MaintenanceLE

Seite 19 - LE Operation

17-G 1/01Pilot Adjustment for FultonLoNOx Burner.a. Close downstream main shut offvalve.b. Start boiler and check flame sig-nal on pilot, lock prog

Seite 20 - 14-G 1/01

18-G 1/01Troubleshootinga. The following troubleshootingguide will assist in the diagnosis andthe correction of minor field prob-lems. It contains

Seite 21 - Maintenance

19-G 1/01Problem Cause RemedyFlame Failure 5. Scanner Check for dirt on flame scanner and clean. Check for proper location of detector.6. Flame Sa

Seite 22 - 16-G 1/01

20-G 1/01Problem Cause RemedyPoor Combustion 1. Refractories Check refractories to see if they are plugged with soot or broken in pieces. Clean or

Seite 23 - LE Maintenance

21-G 1/01Problem Cause RemedyBoiler is Surging 1. Steam traps blowing Check traps to see if they are clean or replace as necessary.through2. Perc (

Seite 24

22-G 1/01Problem Cause RemedyWater pump will not 1. Scale on probes Check and clean or replace as necessary.come on at times2. Bad Pump Contactor C

Seite 25

23-G 1/01PartsLE

Seite 26

ProductBulletinProduct Bulletin2010-001PBThe Fulton Companies972 Centerville RoadPulaski, N.Y. 13142Date: January 22, 2010Subject: Water Chemistry Req

Seite 27

24-G 1/01

Seite 28

25-G 1/01Spare Partsa. It is important that the correctreplacement part is fitted to yourFulton Gas Fired Steam Boiler.b. When ordering replacement

Seite 30 - 24-G 1/01

Boiler Description/Instructions Gas Fired Boiler227-G 1/01

Seite 31 - LE Parts

Description/InstructionsTransformer ScrollGasketsSteam GaugeAssemblyGauge GlassValveTo O.P.C.*To H.P.C.*Burner MotorGauge GlassValveGauge GlassA

Seite 32 - 26-G 1/01

BIJON/OFF GAS HEADCAN PIVOT 360°MODULATED GAS HEAD ISFIXED ABOVE FAN HOUSINGCLEARANCE REQUIRED FORBURNER REMOVALETop ViewFront ViewSide ViewKPNFAMSHRQ

Seite 33 - 27-G 1/01

ffsstd-pds-2011-1222SpecificationsModels ICS/ICX/FB 4 6 9.5 10 15 20 25 30 50 60Boiler ConnectionsN. Steam Outlet 15 PSI 1” 1” N/A 1.5” 2” 3” 3” 3” 4

Seite 34

30-G 1/01Description/InstructionsIEKKJKDCHBAGF

Seite 35

Description/InstructionsLocating the Boilera) The boiler should be located in drysurroundings on a level base, makingsure that there is sufficient ro

Seite 36

32-G 1/01Description/InstructionsVentVentReturnCold WaterSupplySightGlassUnionPump/StrainerThermometerAquastatDrainCondensateReturnTankBlowdownSepara

Seite 38 - PREVIOUS PAGES

Description/InstructionsSafetyValveWaterColumn andSightGlassElectricControlPanelGas FiredSteam BoilerShutOffValveCheckValvesFastOpeningValveBlowdownVa

Seite 39 - Separator

Description/InstructionsBoiler Installation The Steam Supply — Pipe thesteam supply line from the top rightside of the boiler. The Steam Safety Valv

Seite 40 - Steam Boiler

The Blow-Off Valve — There are twoblow off valves on the boiler: Themain valve at the rear of the boilerand the water gauge glass blow offvalve. The

Seite 41 - Steam Outlet

36-G 1/01Water Gauge & Gauge GlassInstallation instructionsNOTEOnly properly trained personnelshould install and maintain watergauge glass and co

Seite 42

Water Supplya) Feed water contains solids anddissolved gases. These may promoteincrustation of scale; foaming, prim-ing, surging, and solids in steam

Seite 43

38-G 1/01pH: pH is a measure of the degreeof acid or base of solution. NormalpH ranges of 6.5-9.0 will have littleinfluence on the corrosion rate ofc

Seite 44

39-G 1/01Electrical Requirementsa) Connect wiring as shown in the wiring diagram which is furnishedinside the electrical control panel box.b) Be sur

Seite 45

40-G 1/01Conventional Ventinga) The stack should rise continuouslyto the connection with the chimney,and should contain no more than twobends at 45 a

Seite 46

41-G 1/01Description/InstructionsExhaust Side Wall Venting (UL andMEA Approved- MEA File Number68-79-E Vol. 2 ) a) Boilers for which sidewall ventin

Seite 47

42a-G 1/01Installation Check Points1) Make sure all piping connectionsare complete and tight.2) Make sure the pressure controlsare adjusted properly

Seite 48

IntroductionThis manual is provided as a guideto the correct operation and mainte-nance of your Fulton Gas FiredSteam Boiler, and should be perma-nent

Seite 49

42b-G 1/01

Seite 50 - 42b-G 1/01

43D-G 1/01Operation3

Seite 51

43b-G 1/01

Seite 52 - 43b-G 1/01

44-G 0/01Starting the Gas Fired Boiler Stop! Make sure you have readand followed all previous safetyinformation.Check with local authorities whereap

Seite 53

OperationGas Burner Set UpNOTE: Refer to Section LE for LOW EMISSIONS BURNERSa) Open the manual gas cocks on thepilot and main lines of the gas head.

Seite 54

46-G 0/01OperationGas Burner Set Up For BoilersEquipped with Modulationa) Modulation is available as anoption on Fulton gas fired steam boil-ers for

Seite 55

47-G 1/01OperationGas Burner Set Up For BoilersEquipped with High-Low-Offa) A gas fired burner equipped forhigh-low-off firing is available as anopt

Seite 56

48-G 0/01OperationWARNINGPrior to the commencement of anywork requiring the removal ofcover plates and the opening of thecontrol panel box, the elect

Seite 57

49-G 1/01OperationBoiler Controls a) Flame safeguard burner control–This is the main control in the panelbox. The programmer in conjunctionwith a s

Seite 58

Maintenance45-G 1/01

Seite 61

Transformer ScrollGasketsSteam GaugeAssemblyGauge GlassValveTo O.P.C.*To H.P.C.*Burner MotorGauge GlassValveGauge GlassAnd ProtectorWater Column

Seite 62

MaintenanceNOTETo ensure the continued safety andefficiency of the boiler, the sched-ule of maintenance outlined in thissection should be adhered to.W

Seite 63

PrimaryAir GateBurnerViewing PortBlast TubeViewing PortBlast TubeScanner (4–15 HP)FlameRod(s)*Gas HeadScanner Location(20–60 HP)BurnerPlateAir Deflect

Seite 64

Furnace Refractory ReplacementProcedure a) Remove the burner plate and topplate assembly up and out of the scrollassembly.b) Remove the stainless st

Seite 65

56-G 1/01Recommended DailyMaintenance Schedulea) The following procedures should becarried out daily. They are designed toprevent the build up of s

Seite 66

57-G 1/01Maintenanceg) Remove brass pipe plug at thecross connection below water columnand clean nipple into boiler. Boilermust be cold and water le

Seite 67

g) Replace hand hole gasketsusing the following procedure:1) Remove the hand hole assemblyusing a 1-1/4" tee handle wrench or 1-1/4" 1/2&q

Seite 68

59-G 1/01MaintenanceTroubleshootinga) The following trouble shootingguide will assist in the diagnosis andthe correction of minor field prob-lems. I

Seite 69

60-G 1/01Problem Cause RemedyFlame Failure 5. Flame Rod Adjustment Check flame rod for carbon buildup and clean ifor UV Scanner necessary. Check fl

Seite 70

1-G 1/01ContentsSection Safety Warnings & PrecautionsFor Boilers with Low Emissions Burner OnlyDescription/InstructionsSpecifications & D

Seite 71

61-G 1/01MaintenanceProblem Cause RemedyPoor Combustion 1. Refractories Check refractories to see if they are plugged with soot orbroken in pieces.

Seite 72

62-G 1/01MaintenanceProblem Cause RemedyBoiler will not 4. Scale Built up in boiler Refer to Section 2 “Pressure Vessel Cleaning”.maintain pressure5

Seite 73 - 6-G 1/01

63-G 1/01MaintenanceProblem Cause RemedyPump runs but does 1. Vapor locking of pump. Allow system to cool down, check steam trapsnot put water into

Seite 74 - 6-G 1/01

Parts56-G 1/01

Seite 76 - 67-G 1/01

66-G 1/01PartsSpare Partsa) It is important that the correctreplacement part is fitted to yourFulton Gas Fired Steam Boiler.b) When ordering replacem

Seite 77 - 68-G 1/01

Parts5-60-100 Instruction Manual, Fuel-Fired 2 0.915-60-165 Certification Papers5-60-164 Boiler Documentation for Export BoilersBoiler Shell Parts5-1

Seite 78 - 69-G 1/01

Parts5-21-302 Steel Jacket 10 HP - No Holes Cut 100 45.455-21-303 Steel Jacket 15 HP - No Holes Cut 115 52.275-21-304 Steel Jacket 20 HP - No Holes C

Seite 79 - 70-G 1/01

PartsBurner Assembly - Parts (Common)2-40-605 1/3 HP 115/230/60/1 Burner Motor 3450 RPM 21 9.552-40-606 1/3 HP 230/460/60/3 Burner Motor 3450 RPM 20

Seite 80 - 71-G 1/01

Parts2-30-118 Air Switch 4-100 HP 0.72 0.335-20-019 Burner Plate Gas - 4 HP 1 0.455-20-007 Burner Plate Gas - 6 & 10 HP 1 0.455-20-055 Burner Plat

Seite 82 - 73-G 1/01

Parts2-30-102 1/2" Gas Pressure Regulator RV 48 0.7 0.322-30-104 1" Gas Pressure Regulator - RV 53 1.5 0.682-30-105 1-1/4 " Gas Pressur

Seite 83 - 74-G 1/01

Parts7-30-025 Burner Plate Assembly - 4 HP - Natural Gas 7 3.187-30-026 Burner Plate Assembly - 6 HP - Natural Gas 8 3.647-30-123 Burner Plate Assembl

Seite 84 - 75-G 1/01

Parts2-12-018 10" Water Gauge Glass- MM 0.06 0.032-12-071 12" Water Gauge Glass 0.07 0.032-12-063 14"Water Gauge Glass 0.08 0.042-30-15

Seite 85 - 76-G 1/01

Parts2-45-106 Green Panel Box Indicating Light - 120V 0.1 0.052-45-107 White Panel Box Indicating Light -120V 0.1 0.052-45-108 Amber Panel Box Indic

Seite 86 - 77-G 1/01

Parts2-40-161 Mini Peeper For All 7800 0.5 0.232-40-270 Base For All 7800 0.5 0.232-40-272 Display Module for 7800 Controls English (Also Available i

Seite 87 - 78-G 1/01

Parts2-30-068 3/4"-100# Safety Valve 2 0.912-30-069 3/4"-125# Safety Valve 2 0.912-30-070 3/4"-150# Safety Valve 1.4 0.642-30-071 3/4

Seite 88 - 79-G 1/01

Parts5-10-397 Tee Handle Wrench 2.7 1.232-20-110 Fan Puller - 5/8" Hub 2 0.912-20-115 Fan Puller - 1" Hub 2 0.91Barometric Controls2-30-0

Seite 89 - 80-G 1/01

Parts2-12-528 Scroll Gasket - 4 HP 1 0.452-12-529 Scroll Gasket - 6-15 HP 1 0.452-12-530 Scroll Gasket- 20-30 HP 1 0.452-12-531 Scroll Gasket- 40-60 H

Seite 90 - -G 1/01

79-G 1/01Parts

Seite 91 - Gas Train Components

80-G 1/01PartsPart No.* Burner Motor (1)RPM HP2-40-605 1/3 HP 115/230/60/1 3450 4-152-40-606 1/3 HP 230/460/60/3 3450 4-152-40-603 1/3 HP 110/2

Seite 92 - 4 to 50 HP

Safety Warnings/Precautions13-G 1/01

Seite 93 - Panel Box Parts

81-G 1/01PartsGas BurnerIgnition AssemblyGas Burner Components

Seite 94 - 85-G 1/01

82-G 1/01PartsGas Head AssembliesPart No. Complete Gas Head Assembly HP7-54-1000 Natural Gas 47-54-1001 Natural Gas 67-54-1002 Natural Gas 107-54-10

Seite 95 - Warranty

83-G 1/01Parts1291011683254768910111Gas Head Assembly (CSD-1)4 to 50 HPGas Head Assembly (CSD-1)60 HP

Seite 96 - 87-G 1/01

84-G 1/01PartsWater LevelRelayContactor/Overload–3 Phase (Upon Request) orStarter Relay–1 PhaseFor Feed WaterPump MotorFlameSafe Guard/Burner Control

Seite 97

85-G 1/01Parts1412(LocatedInBoiler)913111012615845373Water Column - Parts Part No. Water Column Bottle Casting (1) HP5-20-022 Water Column Bottle Ca

Seite 98 - 89-G 1/01

Warranty68-G 1/01

Seite 100 - 91-G 1/01

Standard Warranty for Fulton Boilers Warranty Valid for Models ICS, ICX, ICW, ICXW, VMP, VMPW, FB-A, FB-F, FB-L, FB-S, FB-W Five (5) Year (60 Mont

Seite 102

Extended Warranty for Fulton Skid Mounted Steam Boilers Warranty Valid for Models ICS, ICX, VMP, FB-A, FB-F, FB-L, FB-S Ten (10) Year Material and W